Back to insights

Aquifer Thermal Energy Storage in the spotlight

Low-carbon buildings need energy systems that respond to how heating and cooling demand changes across the year.

Aquifer Thermal Energy Storage (ATES) can make an important contribution to low-carbon heating and cooling where ground conditions allow it. The principle is well established in the Netherlands, successful application depends on the building, its energy centre, the aquifer and the controls operating as one seasonal energy system.

3 key benefits of a carefully integrated system:

  • reduced natural gas use and CO₂ emissions
  • lower operating costs
  • efficient use of renewable electricity through heat pumps

Energy balance is the design challenge

Deerns has worked with ATES since the mid-2000s across hospitals, schools, offices and large life science developments. Our experience shows that performance depends on understanding how a building will actually use heat and cold throughout the year.

In a typical Dutch system:

  • Summer: groundwater from the cold well cools the building and returns to a warm well
  • Winter: water from the warm well supplies a heat pump for building heating. The cooled water then returns to the cold well for the next cooling season.

For ATES to remain effective, the heat and cold stored and extracted must remain in balance over time. In the Netherlands, this is also important for permitting. Predicting building demand is therefore central to the design.

In recent years, that prediction has become more difficult. Average ambient temperatures have risen compared with data used for earlier projects, while better insulation and glazing reduce heating demand. Internal heat gains and ventilation can keep cooling demand high, creating buildings that require considerably more cooling than heating.

Deerns uses operating scenarios and modelling based on:

  • Seasonal heating and cooling demand, including extreme climate years
  • Expected occupancy, ventilation and peak-use conditions
  • Well capacity, annual volume limits and the control strategy needed to maintain balance

This modelling also helps determine how an ATES system can respond when the seasonal balance shifts. Dry coolers are becoming increasingly important in this respect. During cold weather, they can reject surplus heat to outside air while generating additional cold for storage in the aquifer. This provides a way to correct seasonal imbalances and maintain system performance without relying on conventional mechanical cooling.

Designing around real-world constraints

Two large-scale developments illustrate how ATES design needs to respond to the specific characteristics of a site rather than treating the system in isolation.

On a large mixed-use urban development, existing wells and space constraints limited both well locations and available capacity. The buildings required more cooling than was available from the ATES system. The solution therefore combined ATES with dry coolers to meet the remaining demand and maintain system balance. The mix of office and residential uses also created an opportunity to align different demand profiles: residential heating could generate cooling that was subsequently used by the offices, making more effective use of the available capacity.

A different challenge arose on a large technology campus, where several buildings are connected to a shared ATES network and come online in phases. With annual demand of approximately 3,000 MWh of heating and 4,000 MWh of cooling, the challenge is maintaining balance as buildings with different demand profiles are added to the network. Individual energy centres can serve each building, while the wells remain a shared resource. This requires flow, pressure, operating modes and balancing measures to be considered at network level from the outset.

Together, these examples show why ATES performance depends not only on the technical design of individual buildings, but on how demand, infrastructure and available subsurface capacity interact across the wider development.

Experience across the system

The aquifer remains fundamental to the feasibility of any ATES system. Capacity, groundwater quality, subsurface gases, particulates and geology can all influence the solution. Specialist subsurface assessment and borehole construction are therefore important to establishing feasibility and managing investment risk.

Deerns works closely with specialist subsurface partners, bringing their expertise together with the building and energy systems to develop an integrated ATES solution.

A robust approach rests on 3 priorities:

  • Establish conditions early: Work with specialist subsurface partners to understand aquifer capacity, water quality and drilling conditions.
  • Design the systems together: Integrate the building energy centre and ATES system, using realistic demand modelling.
  • Plan for the long term: Incorporate controls, monitoring, maintenance and aftercare into the engineering strategy from the outset.

This integrated approach also matters after handover. Weather, occupancy and building use will change over time, affecting the balance between heating, cooling and aquifer storage. Deerns’ operational experience highlights the importance of monitoring these changes and understanding how interventions in one part of the system can affect performance elsewhere. Knowledgeable control and maintenance are therefore essential to maintaining ATES performance over the long term.

Dutch experience with wider relevance

ATES cannot simply be copied from the Netherlands into another country. Suitable aquifers, groundwater conditions, regulation, permitting and drilling expertise must be established locally. Even within the Netherlands, unpredictable geology can make other energy solutions more appropriate.

The broad engineering expertise however is globally applicable. Where local conditions support ATES, Dutch experience demonstrates the value of early feasibility studies, dynamic energy modelling, integrated building services design, adaptable controls and long-term monitoring. Local hydrogeological expertise can then be combined with proven knowledge of the above ground energy system.

For Deerns, this provides a credible route to applying ATES expertise more widely: assess suitability first, design for real energy balance, and work with specialist local partners where subsurface knowledge is essential. When these elements align, ATES can form an efficient part of a low carbon energy strategy for individual buildings, mixed-use developments and multi-building campuses.

Related thoughts

Let’s talk


Rouven Nieuwenburg

Sector Director Real Estate

Array